Product Illustration
In the event of
top loading, the overfill prevention and static grounding protector will
interlock with the quantity loading control system to inspect the tank liquid
level through the liquid level switches and check the grounding condition by
electrostatic grounding clip.
when the liquid
level reaches the sensor or the grounding resistance out of limited,
acousto-optic alarm will reminder and output signal to quantitative loading
control system, to prevent overfill and ensure static grounding.
Technical
Parameters
1. Explosion-protection grade: Exdia II BT4
2. IP grade: IP65
3. Monitoring set point: < 60Ω
4. Alarm volume: >90dB(Linear distance is 30cm)
5. Working current: <35 mA
6. Working voltage: 220V AC
7. Response time: < 2s
8. Output signal: 10A, 30V DC or 10A, 250V AC
9. Temperature range: -40℃~ 60℃
Constitute Forming
1.
Controller
2.
Monitor
Box
3.
UZK-02
liquid level switches
4.
Homing
sensor
5.
SC-03
electrostatic grounding clip
6.
Work
status board
7.
Grounding
wire 3m.